Home Inspection Report
27 Larchwood Crescent
Peterborough, ON K9K 0A0
Property information
- Client
- Morgan & Riley Ashford
- Inspection
- October 24, 2026 · 10:00 AM
- Property type
- Two-storey detached
- Year built
- 2004
- Size
- 2,150 sq ft
- Weather
- Overcast, 9 °C, dry
- Occupancy
- Occupied, furnished
Company information
Northline Home Inspections
Alex Morgan
Licence: RHI #0000 (sample)
Meet the inspector
Alex Morgan
Northline Home Inspections · RHI #0000 (sample)
Registered Home Inspector serving the Kawarthas. Sample profile for the Expert Check website.
Scope of inspection
If you are reading this report but did not hire us to perform the original inspection, please note that it is likely that conditions related to the home have probably changed, even if the report is fairly recent. Just as you cannot rely on an outdated weather report, you should not rely on an outdated inspection report. Minor problems noted may have become worse, recent events may have created new issues, and items may even have been corrected and improved. Don't rely on old information about one of the biggest purchases you'll ever make. Remember that the cost of a home inspection is insignificant compared to the value of the home. Protect your family and your investment, and please call us directly to discuss the report you're reading for this property so that we can arrange for a re-inspection. This was a limited visual inspection of apparent conditions in the readily and easily accessible areas that existed at the time of the inspection. As such, this report was a "snapshot" in time. Only areas specifically mentioned in this report have been inspected and those areas not mentioned are not part of this inspection. No warranties or guarantees are given or implied. ENVIRONMENTAL CONDITIONS: Unless otherwise indicated, the inspection and report do not address, and are not intended to address, the possible presence of, or danger from, any potentially harmful substances and environmental hazards including, but not limited to, radon gas, lead paint, asbestos, urea-formaldehyde, toxic or flammable chemicals, and hot water and airborne hazards. CODES: No check is made for building/housing code conformance. The Inspector always recommends having a qualified professional examine every item in this report and make the needed repairs. Please note that all residences should have C.O. and fire/smoke detectors. It is the responsibility of the client/resident to ensure that these are placed in sufficient quantity throughout the home.
Standards of Practice
This inspection follows: InterNACHI Standards of Practice
Pre-inspection agreementSigned
Signed in person by Morgan & Riley Ashford on October 26, 2026.
Morgan & Riley Ashford
October 26, 2026
Alex Morgan
October 26, 2026
Summary
SAFETY HAZARD (4)
- 1.9.1Railings, Guards & HandrailsExteriorLoose railing or guard noted — safety concern. Resecure to structure before use.
- 8.5.1Hot Water SourcePlumbingTPR (temperature-pressure relief) valve discharge pipe missing or improperly installed. The discharge pipe must terminate within 6 inches of the floor or discharge to exterior — a safety requirement. Have licensed plumber correct.
- 9.8.1Electrical WiringElectricalOpen junction box observed — cover plate missing. Install appropriate cover — open junction boxes are a shock hazard.
- 12.7.1Presence of Smoke and CO DetectorsDoors, Windows & InteriorCarbon monoxide detector missing — safety concern. Required in Ontario for all homes with fuel-burning appliances or attached garages. Install on each level near sleeping areas.
REPAIR NEEDED (6)
- 1.4.1Vegetation, Surface Drainage, Retaining Walls & GradingExteriorNegative grading observed at foundation — water drains toward structure. Regrade soil to slope away from foundation minimum 6 inches over 10 feet.
- 1.12.1Exhaust HoodsExteriorDryer vent termination screen clogged with lint. Clean immediately — a blocked dryer vent is a fire hazard.
- 2.1.2Roof CoveringRoofingDamaged or cracked shingles noted. Prone to water infiltration. Repair or replace affected areas promptly.
- 9.9.1Panelboards & BreakersElectricalDouble-tapped breakers observed — multiple wires on a single breaker terminal. Most breakers are rated for only one conductor per terminal. Have licensed electrician evaluate and correct.
- 9.12.1GFCIsElectricalGFCI protection missing at exterior outlets — required at all exterior locations. Have licensed electrician install.
- 16.5.1Ceiling, Walls & Firewalls in GarageAttached GarageGaps or holes in garage ceiling or wall drywall. Repair with appropriate drywall to restore fire separation — the garage firewall is a critical life safety element.
MONITOR (3)
- 2.1.1Roof CoveringRoofingRoof covering appeared to be approximately mid-life based on wear patterns observed. Continued monitoring and routine maintenance are recommended.
- 5.1.1BasementBasement, Foundation, Crawlspace & StructureFloor slab cracking noted. Minor cracking is common and typically not structural. Monitor for changes — significant heaving or displacement warrants further evaluation.
- 8.5.2Hot Water SourcePlumbingWater heater is at or approaching typical service life of 10-12 years. Budget for replacement — water heater failure can cause significant water damage.
MAINTENANCE (6)
- 1.3.1Wall Covering, Flashing & TrimExteriorDeteriorating mortar joints observed at masonry. Tuckpointing by a qualified mason is recommended.
- 1.10.1WindowsExteriorWindow caulking deteriorating at frame or sill. Recaulk to prevent water intrusion.
- 2.6.1Gutters & DownspoutsRoofingDownspout discharging too close to foundation. Extend minimum 6 feet away from foundation to prevent moisture intrusion and foundation issues.
- 6.1.2Heating System InformationHeatingAnnual furnace service and inspection by a qualified HVAC technician is recommended. Regular maintenance extends equipment life and ensures safe, efficient operation.
- 12.2.1WindowsDoors, Windows & InteriorWindow not operating smoothly. Clean track and lubricate hardware — stiff operation indicates debris or worn hardware.
- 14.2.1Clothes DryerLaundryDryer vent cleaning recommended. Lint accumulation in dryer venting is a leading cause of residential fires — clean annually or more frequently with heavy use.
IMPROVE (2)
- 10.2.1Insulation in AtticAttic, Insulation & VentilationAdditional insulation recommended to achieve current code minimum R-value for Ontario climate zone. Consult qualified insulation contractor for current requirements and installation.
- 11.4.1Bathroom Exhaust Fan / WindowBathroomsRecommend running bathroom exhaust fan during showering and for at least 20 minutes afterward to adequately remove moisture from the space.
Asking the seller for repairs? Pick findings and send a repair request.
- 1.3Wall Covering, Flashing & Trim1 Maint
- 1.4Vegetation, Surface Drainage, Retaining Walls & Grading1 Repair
- 1.9Railings, Guards & Handrails1 Safety
- 1.10Windows1 Maint
- 1.12Exhaust Hoods1 Repair
System Details
- Wall Covering Material
- Brick
- Trim Material
- Aluminum
- Driveway Material
- Asphalt
- Walkway Material
- Concrete
1.2Eaves, Soffits & Fascia
- 1.2.1SATISFACTORY
Aluminum soffits and fascia were present and appeared intact with no visible damage or separation.
1.3Wall Covering, Flashing & Trim
- 1.3.1MAINTENANCERoutine
Deteriorating mortar joints observed at masonry. Tuckpointing by a qualified mason is recommended.
1.4Vegetation, Surface Drainage, Retaining Walls & Grading
- 1.4.1REPAIR NEEDEDSoon
Negative grading observed at foundation — water drains toward structure. Regrade soil to slope away from foundation minimum 6 inches over 10 feet.
1.8Porches, Patios, Decks, Balconies & Carports
- 1.8.1SATISFACTORY
Wood deck appeared in serviceable condition overall. No significant structural deficiencies were noted at accessible areas.
1.9Railings, Guards & Handrails
- 1.9.1SAFETY HAZARDImmediate
Loose railing or guard noted — safety concern. Resecure to structure before use.
1.10Windows
- 1.10.1MAINTENANCERoutine
Window caulking deteriorating at frame or sill. Recaulk to prevent water intrusion.
1.12Exhaust Hoods
- 1.12.1REPAIR NEEDEDSoon
Dryer vent termination screen clogged with lint. Clean immediately — a blocked dryer vent is a fire hazard.
System Details
- Roof Covering Material
- Asphalt Shingles
- Estimated Roof Age
- 10-15 Years
- Number of Layers
- 1 Layer
- Roof Style
- Gable
- Gutter Material
- Aluminum
- Inspection Method
- Drone
Section Limitations
Inspection does not guarantee roof is leak-free.
2.1Roof Covering
- 2.1.1MONITORMonitor
Roof covering appeared to be approximately mid-life based on wear patterns observed. Continued monitoring and routine maintenance are recommended.
- 2.1.2REPAIR NEEDEDSoon
Damaged or cracked shingles noted. Prone to water infiltration. Repair or replace affected areas promptly.
2.2Flashing
- 2.2.1SATISFACTORY
Pipe boot flashings at plumbing and mechanical penetrations appeared intact with no visible cracking or separation.
2.6Gutters & Downspouts
- 2.6.1MAINTENANCERoutine
Downspout discharging too close to foundation. Extend minimum 6 feet away from foundation to prevent moisture intrusion and foundation issues.
3.5Wood-Burning Stove
- 3.5.1NOT PRESENT
This item was not present.
System Details
- Foundation Type
- Poured Concrete
- Basement Type
- Full Basement
- Basement Finish
- Partially Finished
- Sump Pump
- Not Present
- Floor Structure
- Wood Joists
5.1Basement
- 5.1.1MONITORMonitor
Floor slab cracking noted. Minor cracking is common and typically not structural. Monitor for changes — significant heaving or displacement warrants further evaluation.
System Details
- Heating System Type
- Forced Air Furnace
- Fuel Type
- Natural Gas
- Distribution
- Ductwork
- Filter Size
- 16 x 25 x 1 in
6.1Heating System Information
- 6.1.1SATISFACTORY
Gas forced-air furnace was present and operational. The system responded to the thermostat and produced heat at the time of inspection.
- 6.1.2MAINTENANCERoutine
Annual furnace service and inspection by a qualified HVAC technician is recommended. Regular maintenance extends equipment life and ensures safe, efficient operation.
System Details
- Cooling System Type
- Central Air
- Condenser Location
- Ground Level - Side
Section Limitations
Cooling system not tested when outdoor temperature below 60F.
7.1Cooling System Information
- 7.1.1NOT INSPECTED
This item was not inspected.
System Details
- Supply Pipe Material
- Copper
- Drain Pipe Material
- ABS
- Water Source
- Municipal
- Waste Disposal
- Municipal Sewer
- Main Shutoff Location
- Basement, front wall
Equipment
Water heater (tank)
- Make
- Bradford White
- Model
- RG250T6N
- Serial
- GJ26543101
- Year
- 2010 · Age: 16 yrs
- Gallons
- 50
- Owned / rented
- Rented (rental sticker)
8.2Water Supply
- 8.2.1SATISFACTORY
Copper supply piping was observed and appeared in serviceable condition at accessible areas.
8.5Hot Water Source
- 8.5.1SAFETY HAZARDImmediate
TPR (temperature-pressure relief) valve discharge pipe missing or improperly installed. The discharge pipe must terminate within 6 inches of the floor or discharge to exterior — a safety requirement. Have licensed plumber correct.
- 8.5.2MONITORMonitor
Water heater is at or approaching typical service life of 10-12 years. Budget for replacement — water heater failure can cause significant water damage.
System Details
- Service Size
- 100 Amp
- Service Type
- Underground
- Panel Location
- Basement, utility room
- Branch Wiring Type
- Copper (Romex/NM)
- Grounding
- Water Pipe
- Sub-Panels
- None
Equipment
Main panel
- Make
- Siemens
- Amps
- 100
- Main breaker size (A)
- 100
9.8Electrical Wiring
- 9.8.1SAFETY HAZARDImmediate
Open junction box observed — cover plate missing. Install appropriate cover — open junction boxes are a shock hazard.
9.9Panelboards & Breakers
- 9.9.1REPAIR NEEDEDSoon
Double-tapped breakers observed — multiple wires on a single breaker terminal. Most breakers are rated for only one conductor per terminal. Have licensed electrician evaluate and correct.
9.12GFCIs
- 9.12.1REPAIR NEEDEDSoon
GFCI protection missing at exterior outlets — required at all exterior locations. Have licensed electrician install.
System Details
- Attic Access
- Scuttle Hole
- Access Location
- Upper hallway closet
- Insulation Type
- Blown Fiberglass
- Insulation Depth
- 6-10 inches
- Ventilation Type
- Multiple Types
- Roof Sheathing
- OSB
Section Limitations
Attic accessed through scuttle hole; limited mobility.
10.2Insulation in Attic
- 10.2.1IMPROVEOptional
Additional insulation recommended to achieve current code minimum R-value for Ontario climate zone. Consult qualified insulation contractor for current requirements and installation.
10.3Ventilation in Attic
- 10.3.1SATISFACTORY
Attic ventilation appeared adequate at the time of inspection. Ridge and soffit ventilation were present providing balanced airflow.
11.4Bathroom Exhaust Fan / Window
- 11.4.1IMPROVEOptional
Recommend running bathroom exhaust fan during showering and for at least 20 minutes afterward to adequately remove moisture from the space.
12.2Windows
- 12.2.1MAINTENANCERoutine
Window not operating smoothly. Clean track and lubricate hardware — stiff operation indicates debris or worn hardware.
12.7Presence of Smoke and CO Detectors
- 12.7.1SAFETY HAZARDImmediate
Carbon monoxide detector missing — safety concern. Required in Ontario for all homes with fuel-burning appliances or attached garages. Install on each level near sleeping areas.
14.2Clothes Dryer
- 14.2.1MAINTENANCERoutine
Dryer vent cleaning recommended. Lint accumulation in dryer venting is a leading cause of residential fires — clean annually or more frequently with heavy use.
16.5Ceiling, Walls & Firewalls in Garage
- 16.5.1REPAIR NEEDEDSoon
Gaps or holes in garage ceiling or wall drywall. Repair with appropriate drywall to restore fire separation — the garage firewall is a critical life safety element.
17.3GFCI
- 17.3.1SATISFACTORY
GFCI protection was present at kitchen counter outlets and tested operational at the time of inspection.
Photo appendix
Left side wall